AFX SERIES® OPERATION MANUAL
SECTION 13:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS)
• All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 379 of 402
Error Source
Code
Category
Error Message
Possible Cause
Resolution
Front panel
Error
78
Error
Data logger rate not
allowed.
Data logging rate set is
invalid
Adjust logging rate
setting
Front panel
Error
79
Event
Data logger is running
Trying to change
configuration settings
while data logging is in
progress. Stop data
logger function before
changing configuration
Stop data logger function
before changing
configuration
Front panel
Error
80
Error
Data logger execution
error.
Error during data logging
Stop data logger function
Front panel
Error
84
Event
Unable to change form
while output is enabled.
Trying to change phase
mode while output is ON.
Phase mode (FORM)
cannot be changed while
output is ON
Turn output OFF first,
then change FORM
Front panel
Error
85
Error
Unable to clear one or
more fault.
Could not clear one or
more faults when
requested
Try recycling power. If
error persists, contact
customer service
Front panel
Error
86
Error
Unable to enable output.
One or more primary
stages failed to enable.
Output ON failed due to
power input stage fault
Try recycling power. If
error persists, contact
customer service
Front panel
Error
89
Error
Digital I/O interface
conflict: Remote inhibit is
active.
Conflict between front
panel and Remote Inhibit
input level
Resolve conflict. Check
input to Remote Inhibit
Front panel
Error
90
Error
Digital I/O interface
conflict: Remote enable is
active.
Conflict between front
panel and Remote
Enable input level
Resolve conflict. Check
input to Remote Enable
Front panel
Error
91
Error
Internal error: Unknown
phase mode.
Selected Phase Mode
(FORM) is unknown
Try recycling power. If
error persists, contact
customer service
Front panel
Error
92
Error
Unable to disable output.
One or more primary
stages failed to disable.
Output OFF failed.
Attempt to disable one or
more inverter stages
failed
Turn Unit off with Circuit
Breaker
Front panel
Error
93
Error
Internal error: Cannot
configure timer.
Timer Configuration Error
Reset front panel
Front panel
Error
94
Error
Internal error: Cannot
create timer.
Timer Creation Error
Reset front panel
Front panel
Error
95
Error
Digital I/Os interface
conflict: Serial interface
flow control is active.
RS232 or USB interface
error
Check RS232 or USB
settings
Front panel
Error
96
Error
Data logger storage error.
Error saving
measurement data to
selecting memory device.
Memory device may have
been removed
Check for Memory device
presence
Front panel
Error
97
Error
Output enable in
progress.
Waiting to turn output
off. Changing from
Output ON to Output OFF
state
Wait for power stages
and inverters to fully
engage
Front panel
Error
98
Error
DC Voltage not allowed in
"AC mode".
Setting conflict. Setting
does not match mode
Check setting