Type 8756
Setting and operation
english
51
The product status indicator flashes.
Go to
Sensor
>
Parameter
>
Advanced
>
Limit on low cutoff
Set the cut-off limit in the range that is displayed.
The cut-off limit is set.
8.2.4
Flush bubbles from the pipe (MFC with
pump)
To make sure that there are no bubbles in the pipe, do the follow-
ing procedure:
Fill the pipe as described in the chapter
damaging the pump (MFC with pump) [
.
Connect the product to the Bürkert Communicator software.
Refer to chapter:
Connect the product to the Bürkert Com-
In the Bürkert Communicator software, select the product.
Go to
Controller
>
Set-point value source
> Choose
Open-
loop control mode
WARNING!
Risk of injury from flowing fluid.
While the procedure is running, the mass flow rate value can be
higher than the nominal flow rate value.
▶
Before running the procedure, make sure that no danger can
occur if the mass flow rate value increases.
The product status indicator is orange.
A check-function event is generated.
Go to
Actuator
>
Actuating variable
Set 50% > wait for 5 seconds > set 0% > wait for 5 seconds.
Set 60% > wait for 5 seconds > set 0% > wait for 5 seconds..
If the product still detects bubbles in the pipe, then contact
Bürkert.
Go to
Controller
>
Set-point value source
> Choose
Auto-
matic
The product operates normally.
8.2.5
Flush bubbles from the pipe (MFC with
proportional valve)
To make sure that there are no bubbles in the pipe, do the follow-
ing procedure:
Make sure that the product is filled with fluid.
Connect the product to the Bürkert Communicator software.
Refer to chapter:
Connect the product to the Bürkert Com-
In the Bürkert Communicator software, select the product.
Go to
Controller
>
Set-point value source
> Choose
Open-
loop control mode
WARNING!
Risk of injury from flowing fluid.
While the procedure is running, the mass flow rate value can be
higher than the nominal flow rate value.
▶
Before running the procedure, make sure that no danger can
occur if the mass flow rate value increases.