Type 8756
Technical data
english
32
0...5/10 V
▪
Maximum current: 20 mA
▪
Resolution: 10 mV
Tab. 45: Analogue output for the measured value, product variant
Analogue
0/4...20 mA
▪
Maximum input impedance: 200 Ω
▪
Resolution: 5 µA
0/5...10 V
▪
Minimum input impedance: 20 kΩ
▪
Resolution: 2.5 mV
Tab. 46: Analogue input for the set-point value, product variant
Analogue
0...0.2 V
to activate level 1
1...4 V or open
to activate level 2
5...28 V
to activate level 3
Tab. 47: Digital input, product variant Analogue
Minimum temperature
rating of the cable to be
connected to the field
wiring terminals:
75 °C
Tab. 48: Temperature
4.6.4
Mass Flow Controller for modular
actuator
ATTENTION!
▶
For UL-certified components, only use limited power circuits
of "NEC Class 2".
Operating voltage
24 V DC ±10 %
Maximum power con-
sumption
4 W plus max. 65 W (power consump-
tion of the actuator)
Communication interface büS and CANopen. The communica-
tion type can be chosen with the
Bürkert Communicator software.
PWM signal (open col-
lector)
22 kΩ-pull-up resistor and free wheel-
ing diode, both to 24 V
Tab. 49: General electrical data, product variant büS/CANopen
Operating voltage
24 V DC ±10 %
Maximum power con-
sumption
4 W plus max. 65 W (power consump-
tion of the actuator)
PWM signal (open col-
lector)
22 kΩ-pull-up resistor and free wheel-
ing diode, both to 24 V
Tab. 50: General electrical data, product variant Analogue
Relay type
Change-over relay with 1 normally
closed contact (break contact) and 1
normally open contact (make contact).
Both contacts are free of potential