Type 8756
Troubleshooting
english
66
Cause
Solution
The product is connected to
büS, but does not find the pro-
cess value to be processed.
Make sure that you have
correctly allocated the pro-
cess value.
Check the assigned büS
participant that is defective.
Make sure that the assigned
büS participant provides the
cyclic data.
The sensor, the internal
memory or the product is de-
fective.
Contact the manufacturer,
because maintenance is
needed.
10.1.6
Product status indicator is red (MFC
büS/CANopen with proportional valve
or for modular actuator)
Identify the cause to solve the problem:
Cause
Solution
The supply voltage is out of the
error range. The product can be
damaged.
Operate the product within
the specifications. If the
product status indicator is
still red, then send the
product back to Bürkert.
Incorrect Autotune or Autotune
aborted.
Make sure that the fluid
flows through the product.
Do the Autotune again.
Cause
Solution
büS error or CANopen-bus er-
ror, for example a short circuit.
Make sure that the product
is correctly wired.
The product is connected to
büS, but cannot find any field-
bus participants.
Make sure that the product
is correctly wired.
Operate the product with
other fieldbus participants.
The product is connected to
büS, but does not find the pro-
cess value to be processed.
Make sure that you have
correctly allocated the pro-
cess value.
Check the assigned büS
participant that is defective.
Make sure that the assigned
büS participant provides the
cyclic data.
The sensor, the internal
memory or the product is de-
fective.
Contact the manufacturer,
because maintenance is
needed.
10.1.7
Product status indicator is orange
(MFM büS/CANopen)
Identify the cause to solve the problem:
Cause
Solution
The product is connected to
büS and searches assigned
fieldbus participant.
Wait until the product has
found assigned fieldbus par-
ticipants.