Setting and operation
english
56
8.5.2
Increase the data transmission
speed
If the data transmission speed is increased, then the product
provides more cyclic process-data.
For example, the actual value of the mass flow rate is available
once every 100 ms by default. If the data transmission-speed is
increased, then the actual value of the mass flow rate is available
once every 10 ms.
If the data transmission-speed is active simultaneously on
several products in the network, then make sure that the bus
load does not exceed 50%.
To increase the data transmission-speed, do the following:
Energise the bus network.
Connect the product to the Bürkert Communicator software.
Refer to chapter:
Connect the product to the Bürkert Com-
In the Bürkert Communicator software, move the PC mouse
over the büS-stick symbol in the list of devices. If the bus load
is higher than 45%, then do not increase the data transmis-
sion-speed.
If the bus load is less than or equal to 45%, then the data
transmission-speed can be increased. Do the following pro-
cedure:
In the Bürkert Communicator software, select the product.
The product status indicator flashes.
Go to
General settings
>
Diagnostics
>
Inhibit time
.
To increase the data transmission-speed, click
Set diagnostic
mode
. The function
Inhibit time
switches to
Set to default val-
ues
.
The data transmission-speed is increased.
To go back to the default data transmission-speed, click
Set
to default values
. The function
Inhibit time
switches to
Set
diagnostic mode
.
8.6
Operating modes of an MFC
When energising the product for the first time, the product enters
a short initialization phase and then switches to the normal oper-
ating mode. The normal operating mode is described in chapter:
The possible operating modes are described in following table.
Operating mode
Description
Product variant büS/CANopen:
Automatic
Product variant Analogue:
Ana-
log set-point value
Manual set-point value
source that gives the set-point
value (MFC) [
Stored set-point value