Type 8756
Electrical connection
english
41
ATTENTION!
Requirements for the correct operation of the product.
▶
Use a mating female connector with shield-connection trans-
fer at the union nut.
▶
Use a mating male connector with shield-connection transfer
at the union nut.
▶
Use a mating male connector and a mating female connector
that are in metal.
▶
Observe the specifications for the cable and conductors, that
are given by the manufacturer of the mating female or male
connector.
If your product variant is an MFM, then wire the mating female
connector according to the pin assignment of the M12 male
connector in the following figure. Observe the instructions that
are given by the manufacturer of the mating female connector.
M12 thread is internally connected to FE
Fig. 20: MFM Analogue: Pin assignment, 5-pin M12 male con-
nector (A coding)
1
GND for the analogue output
2
24 V
3
GND
4
Not connected
5
Analogue output for the measured value
6
Coding lug
Connect the cable shielding to the mating female connector.
If your product variant is an MFC, then wire the mating female
connector according to the pin assignment of the M12 male
connector in the following figure. Observe the instructions that
are given by the manufacturer of the mating female connector.
Connect the cable shielding to the mating female connector.
Screw the mating female connector to the 5-pin male con-
nector, to the torque that is given by the manufacturer of the
mating female connector.
M12 thread is internally connected to FE
Fig. 21: MFC Analogue: Pin assignment, 5-pin M12 male con-
nector (A coding)
1
GND for the analogue output and the set-point input
2
24 V