10
Troubleshooting
Logano plus GB402 - Subject to technical modifications!
65
V
CY
573
Flow
temperature
< -5 °C
(interruption).
The control unit
receives unrealistic
values from the
flow temperature
sensor.
Check cabling between
SAFe and flow temperature
sensor.
Replace cable if
required.
Check electrical
connection of the SAFe
cable.
Remedy contact
problem if required.
Check resistance values of
temperature sensor
according to table.
Replace temperature
sensor if required.
Check voltage at the
temperature sensor
terminals inside the SAFe
according to table.
Replace SAFe if
resistance values of the
temperature sensor are
correct, but voltage
values are incorrect.
V
CY
574
Flow
temperature
> 130 °C
(short circuit).
The control unit
receives unrealistic
values from the
flow temperature
sensor.
Check cabling between
SAFe and flow temperature
sensor.
Replace cable if
required.
Check electrical
connection of the SAFe
cable.
Remedy contact
problem if required.
Check resistance values of
temperature sensor
according to table.
Replace temperature
sensor if required.
Check voltage at the
temperature sensor
terminals inside the SAFe
according to table.
Replace SAFe if
resistance values of the
temperature sensor are
correct, but voltage
values are incorrect.
V
LP
570
Too many
resets via the
interface.
Too many resets
were carried out
via the interface
within a certain
period.
Please note: this
fault can only be
reset via the button
on the SAFe.
Faults have been
repeatedly reset but not
removed.
Identify the cause for the
faults that have resulted
in the resets and remove
them.
The BC10 has developed a
fault causing constant
resets.
Replace the BC10.
The SAFe has developed a
fault.
Replace the SAFe.
Type
1)
Display
code
Fault
code
Cause
Description
Test procedure/cause
Action
Tab. 21 Fault displays
1) V = interlocking; B = blocking