9
Inspection and maintenance
Logano plus GB402 - Subject to technical modifications!
46
9.6.2
Cleaning the heat exchanger
Dry cleaning the heat exchanger
B
Remove the thermal insulation from the heat
exchanger.
Fig. 50 Heat exchanger thermal insulation
1
Clip
2
Thermal insulation
B
Undo fixing nuts from cleaning covers [1] at the top and
bottom of the heat exchanger.
B
Remove the cleaning covers.
Fig. 51 Opening the cleaning covers
1
Cleaning cover
B
Undo the fixing nuts from the top and bottom of the
condensate tray cover.
B
Remove the cover.
B
Clean the hot gas flues of the heat exchanger
horizontally and diagonally using the long cleaning
blade.
B
Clean the back section of the hot gas flues from below
through the condensate tray using the short cleaning
blade.
Fig. 52 Dry cleaning the heat exchanger
1
Long cleaning blade (available separately)
2
Short cleaning blade (available separately)
B
Screw the cleaning covers back on.
Fig. 53 View of cleaning cover
1
320 kW
2
395-620 kW
CAUTION:
Risk of injury from sharp edges
on the cleaning blades.
B
To avoid injury, wear gloves when cleaning
the boiler using cleaning blades
(accessories).
WARNING:
Risk to life from escaping flue
gas!
B
During installation, look out for faulty
gaskets and ensure they are seated
correctly. Replace faulty gaskets.
B
Replace the gaskets as described
(
Æ
Chapter 9.13).
6720646293-01.1BU
1