10
Troubleshooting
Logano plus GB402 - Subject to technical modifications!
66
V
LL
571
Too many
restarts
despite resets.
15 restarts
occurred in direct
succession. This
means that the
same problem
persisted after the
resets.
Please note: this
fault can only be
reset via the button
on the SAFe.
Faults have been
repeatedly reset but not
removed.
Identify the cause for the
faults that have resulted
in the resets and remove
them.
V
EE
601
Flow
temperature
sensor
measurement.
Successive
measurements of
the flow
temperature
deviate severely
from each other.
Check the boiler sensor
lead.
Replace in case of
damage.
Clean or replace if
contaminated.
Check the plug-in
connection.
Refit plug it is found to
be loose.
Check sensor values
according to table.
Replace the
temperature sensor in
case of deviations.
Check the voltage at the
temperature sensor
according to table.
Replace the SAFe in
case of deviations.
V
EE
612
Return
temperature
sensor
measurement.
Successive
measurements of
the return
temperature
deviate severely
from each other.
Check the boiler sensor
lead.
Replace in case of
damage.
Clean or replace if
contaminated.
Check the plug-in
connection.
Refit plug it is found to
be loose.
Check sensor values
according to table.
Replace the
temperature sensor in
case of deviations.
Check the voltage at the
temperature sensor
according to table.
Replace the SAFe in
case of deviations.
V
EE
613
Flow
temperature
sensor
measurement.
Successive
measurements of
the flow
temperature
deviate severely
from each other.
Check resistance value of
theflow temperature
sensor.
Replace flow
temperature sensor in
case of deviations.
Type
1)
Display
code
Fault
code
Cause
Description
Test procedure/cause
Action
Tab. 21 Fault displays
1) V = interlocking; B = blocking