10
Troubleshooting
Logano plus GB402 - Subject to technical modifications!
58
V
3C
537
No speed.
The SAFe receives
no speed
feedback, although
the fan is
supposed to be
running.
Check cabling between the
SAFe and the fan for
contact separation, breaks
and damage.
Check plug-in connection
at the SAFe and the fan.
Make the contacts
correctly. Replace cable
if required.
If power is available (no
an start), replace fan.
V
3C
538
Fan speed too
low.
The detected
speed is lower
than the specified
speed.
Fan contaminated.
Clean fan if required.
Fan faulty.
Replace fan.
V
3C
540
Excessively
high fan
speed.
The detected
speed is higher
than the specified
speed.
Check PWM signal/SAFe
cabling for contact
separation, breaks and
damage.
Check plug-in connections
for damage.
Make the contacts
correctly. Replace cable
if required.
Replace fan.
V
4A
520
Intelligent high
limit safety
cut-out, flow.
The flow
temperature has
reached a value of
100 °C.
The temperature rise is
monitored by the boiler
sensor. Consequently the
burner is switched off in
good time, making an
occurrence of this fault
message under normal
circumstances unlikely.
Unfavourable hydraulics in
two-boiler systems: boilers
influence each other, e.g.
via the return or flow.
Check hydraulics.
Type
1)
Display
code
Fault
code
Cause
Description
Test procedure/cause
Action
Tab. 21 Fault displays
1) V = interlocking; B = blocking