10
Troubleshooting
Logano plus GB402 - Subject to technical modifications!
61
B
5L
543
No communi-
cation with
the SAFe.
The MC10 does
not receive data
from the SAFe.
Check whether the cable
plugs (BUS cable and
power cable) between
SAFe and MC10 are
correctly plugged in.
Refit plug it is found to
be loose.
Check in the MC10 at
terminals “Mains SAFe”
whether 230 V are present.
Replace the MC10 if
there are not 230 V.
Check whether the cables
(BUS cable and power
cable) between the SAFe
and the MC10 are
damaged.
Replace cable.
Check whether the green
indicator illuminates on the
SAFe.
Replace the SAFe if the
indicator does not
illuminate.
Separate the BUS cable
between SAFe and MC10
and check whether the
boiler enters emergency
mode (runs at 60 °C boiler
water temperature).
Replace the SAFe if the
boiler does not start.
Make replacements to
check whether it is the
SAFe or the MC10 that is
faulty.
Replace the SAFe or
MC10.
If the SAFe remains dark,
wait a short time as the
appliance will not start up if
the SAFe is cold.
Wait up to 30 minutes
and check whether the
green indicator on the
SAFe illuminates again.
Replace the SAFe if that
is not the case.
B
6L
515
Ionisation
signal failure
during
operation.
Ionisation signal
failure during
burner operation.
-
None; the SAFe will try a
restart.
B
6L
514
Flame torn off
within the
flame
stabilisation
time.
No flame signal
was detected
within the
stabilisation time.
-
None; the SAFe will try a
restart.
V
6C
576
Ionisation
current within
the pre-purge
time > 0.9 μA.
A flame signal was
detected during
the pre-purge time.
Check the ionisation
electrode.
Ensure that the metal fibres
of the burner gauze have no
contact with the electrodes.
Check gas valve function.
Check electrode gap on
the ionisation electrode.
Replace ionisation
electrode.
Replace gas valve.
Type
1)
Display
code
Fault
code
Cause
Description
Test procedure/cause
Action
Tab. 21 Fault displays
1) V = interlocking; B = blocking