Commissioning the heating system
Logano plus GB402 - Subject to technical modifications!
30
7.4
Check the system equipment level
In its delivered condition, the burner is fully adjusted for
use with natural gas H or L. Should it be discovered that
the boiler was ordered for the incorrect gas type, convert
the type and update the type plate accordingly.
B
Ask your gas supply utility about the type of gas
supplied.
B
Check that the actual gas type matches the “Gas type”
label.
B
Affix label [2] (supplied with the boiler) over the
appropriate area on the type plate [1] (on the back
panel).
Fig. 27 Updating the type plate
Country
Gas type
Factory settings
AT, BA, BG, BY, CH,
CN, CZ, DE, DK, EE,
ES, FR, GB, GR, HR,
HU, IE, IT, LU, NO, PL,
PT, RO, RU, SE, SI, SK,
UA
Natural gas H or E
(G20)
Factory-set ready for use.
The gas valve is adjusted and sealed.
Wobbe index for 15 °C, 1013 mbar:
• Adjusted to 14.1 kWh/m
3
• Applicable for 11.4 to 15.2 kWh/m
3
Wobbe index for 0 °C, 1013 mbar:
• Adjusted to 14.9 kWh/m
3
• Applicable for 12.0 to 16.1 kWh/m
3
DE
Natural gas L
Factory-set ready for use.
The gas valve is adjusted and sealed.
Wobbe index for 15 °C, 1013 mbar:
• Adjusted to 12.1 kWh/m
3
• Applicable for 11.4 to 12.4 kWh/m
3
Wobbe index for 0 °C, 1013 mbar:
• Adjusted to 12.8 kWh/m
3
• Applicable for 12.0 to 13.1 kWh/m
3
NL
Natural gas L (G25)
Factory-set ready for use.
The gas valve is adjusted and sealed.
Wobbe index for 15 °C, 1013 mbar:
• Adjusted to 11.5 kWh/m
3
• Applicable for 10.85 to 12.4 kWh/m
3
Wobbe index for 0 °C, 1013 mbar:
• Adjusted to 12.2 kWh/m
3
• Applicable for 10.6 to 13.8 kWh/m
3
Tab. 9
Factory settings