Substations
13
Logamatic 4323 - Subject to technical modifications.
95
13.3 Setting boiler raising
This menu will only appear when operating the Logamatic 4323 control unit as a
substation (address > 1)!
The value entered here will be added to the heat demand of the control unit and
thereby increases the demand temperature. This setting is recommended for
compensating temperature losses in systems with long supply lines.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Substation" appears.
Press "Display" to call up a submenu (here: "Minimum Heat-up temp.").
The display shows the selected submenu.
Turn the rotary selector until submenu "Boiler raising" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "10K").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
Substation
50°C
Heat-up temp.
Minimum
Substation
off
Boiler raising
+
Substation
10K
Boiler raising
Input range
Factory setting
Boiler raising
off
1 K – 20 K
off