DHW data
12
Logamatic 4323 - Subject to technical modifications.
89
12.14 Selecting the DHW circulation pump
You can set DHW to be immediately available at the draw-off points via
the "DHW circulat" function.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "DHW" appears.
Press "Display" to call up a submenu (here: "DHW").
The display shows the selected submenu.
Turn the rotary selector until submenu "DHW circulation" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "no").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
DHW DATA
yes
DHW
DHW DATA
yes
DHW circulation
+
DHW DATA
no
DHW circulation
Input range
Factory setting
DHW circulation
yes
no
yes