DHW data
12
Logamatic 4323 - Subject to technical modifications.
82
12.8 External contact (WF1/3)
"Heating once" or "Therm. disinfect" can be initiated (subject to setting) if a zero
volt pushbutton is connected to terminals WF1 and 3 in module FM441.
The thermal disinfection switching program is disabled if "Therm. disinfect" has
been selected.
"Heating once"
If DHW heating has been switched off according to the switching times of the
DHW program, you may start "Heating once" with the pushbutton. The DHW
circulation pump starts simultaneously.
Unlike heating once via the MEC2 programming unit, the "Heating once"
process cannot be cancelled.
"Heating once" will only be stopped when the cylinder has been fully heated.
"Therm. disinfect"
You can start thermal disinfection with the above-mentioned zero volt
pushbutton if you have assigned the external contact to "Therm. disinfect". Any
existing thermal disinfection program will then become ineffective.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "DHW" appears.
Press "Display" to call up a submenu (here: "DHW").
The display shows the selected submenu.
Turn the rotary selector until submenu "External contact WF1/3" is displayed.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "Heating once").
+
+
DHW DATA
yes
DHW
DHW DATA
none
WF1/3
External contact
+