Monitor data
21
Logamatic 4323 - Subject to technical modifications.
109
The set and the actual values for the
flow and room temperatures
are
displayed.
The last line displays one of the following
operating modes
:
–
Constant night
–
Constant day
–
Automatic night
–
Automatic day
–
Holiday
–
Summer
–
Start optimising
–
Stop optimising
–
Screed
–
DHW priority
–
No setback
Turn the rotary selector to scroll through the heating circuit monitor data.
Design temperature adaptation
This value displays the design temperature calculated by adaptation.
Start optimisation
A calculated period, by which the heating system starts its heating operation
prior to the actual switching point, so that the set room temperature is reached
by the actual start time.
Stop optimisation
A calculated period to commence an early setback to save energy.
Turn the rotary selector to scroll through the heating circuit monitor data.
Servomotor
Indicates the calculated regulating pulse in percent.
Example:
–
0 % = no control
–
50 % = servomotor is controlled in a cycle of 10 seconds for 5 seconds in the
direction "Mixer opens" (hotter).
–
-100 % = servomotor is controlled every 10 seconds for 10 seconds towards
"Mixer closes" (colder) (constant).
Circ. pump
Indicates the operating condition of the circulation pump.
Press "Back" to return to the next level up.
MONITOR B2
Constant night
Room 20/19
Flow 60/59
MONITOR B2
Off opt. 30min
On opt. 15min
Size adaptor 75
MONITOR B2
Circ. pump off
Servomotor 50%