Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
73
Setting the hold time
Here you can select a period of time for which the maximum temperature should
be held to dry out the screed.
Turn the rotary selector until submenu "Screed drying Hold max temp" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "20 days").
The display shows the set value.
Release "Display" to save your input.
Setting the setback temperature
Here you can select the steps in which the temperature for drying out the screed
should be set back.
The setback ends at 20 °C.
Turn the rotary selector until submenu "Screed drying Setback by" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "10K").
The display shows the set value.
Release "Display" to save your input.
HEAT CIRC. DATA 2
4 days
Hold max temp
Screed drying
+
HEAT CIRC. DATA 2
20 days
Hold max temp
Screed drying
Input range
Factory setting
Hold maximum temperature
0 days – 20 days
4 days
HEAT CIRC. DATA 2
5K
Setback by
Screed drying
+
HEAT CIRC. DATA 2
10K
Setback by
Screed drying
Input range
Factory setting
Setback by
1 K – 10 K
5 K