Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
56
11.13 Setting flow setback
Since you cannot connect a
remote control
to heating systems set to
"Constant", you may enter a setback value for the "Reduced" and "Hold if cold"
setback types.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here: "Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "Constant").
The display shows the set value.
Release "Display" to save your input.
Turn the rotary selector until "Flow Setback by" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "25K").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
HEAT CIRC. DATA 2
Radiators
Heating system
+
HEAT CIRC. DATA 2
Constant
Heating system
HEAT CIRC. DATA 2
30K
Setback by
Flow
+
HEAT CIRC. DATA 2
25K
Setback by
Flow
Input range
Factory setting
Flow setback
0 K – 40 K
30 K