Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
50
11.8 Maximum room influence
This function will only appear if a remote control has been selected,
but will not be shown for "Room controller" heating systems.
The maximum room influence limits the effect of the actual room temperature
(room temperature hook-up) to the set flow temperature. This value determines
the maximum possible room temperature setback in those rooms that are
supplied via the currently selected heating circuit and where there are no remote
control units installed.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here: "Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Turn the rotary selector until submenu "Max. room infl" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "5K").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
USER INFORMATION
Do not expose the MEC2 programming unit or the BFU remote control to
external heat sources, such as lamps, TV sets, or alternative heat sources.
+
+
HEAT CIRC. DATA 2
Radiators
Heating system
HEAT CIRC. DATA 2
3K
Max room infl
+
HEAT CIRC. DATA 2
5K
Max room infl
Input range
Factory setting
Max. room influence
0 K – 10 K
3 K