Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
58
11.15 Automatic adaptation
This function will only appear if "Radiator", "Convector" or "Underfloor"
has been selected as the heating system.
"Autom adaptation" is not enabled at the factory.
Where a remote control with room temperature sensor is installed in the room,
the heating curve is automatically adjusted to the building by monitoring the
room and flow temperature.
Conditions are:
–
A representative room with reference temperature.
–
Fully opened thermostatic valves in the room.
–
No constantly fluctuating external heat influence.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here: "Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Turn the rotary selector until submenu "Autom adaptation" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "yes").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
HEAT CIRC. DATA 2
Radiators
Heating system
HEAT CIRC. DATA 2
no
Autom adaptation
+
HEAT CIRC. DATA 2
yes
Autom adaptation
Input range
Factory setting
Automatic adaptation
no
yes
no