Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
66
11.22 Boiler raising
If a heating circuit is controlled with an actuator, a higher design value should
be set for the boiler than the normal boiler set value.
The value "Boil.raising" corresponds to the temperature differential between
the set boiler temperature and the set heating circuit temperature.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here: "Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Turn the rotary selector until submenu "Boil.raising" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "10°C").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
HEAT CIRC. DATA 2
Radiators
Heating system
HEAT CIRC. DATA 2
5°C
Boil.raising
+
HEAT CIRC. DATA 2
10°C
Boil.raising
Input range
Factory setting
Boiler raising
0 °C – 20 °C
5 °C