General parameters
9
Logamatic 4323 - Subject to technical modifications.
35
9.6
Automatic maintenance message
You can generate an automatic maintenance message at the operator level
on the MEC2 programming unit display.
You can set the following:
–
Maintenance message by date. Enter the date of the next scheduled service
(01.01.2000 – 31.12.2088).
–
Maintenance according to "Hours run" (only for control units with direct boiler
control).
Call up the service level. "Gen. parameters" is shown as the first main menu.
Press "Display" to call up a submenu (here: "Min outside temp").
The display shows the selected submenu.
Turn the rotary selector until the "automatic maint. message" submenu appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "Date").
The display shows the set value.
Release "Display" to save your input.
Turn the rotary selector one increment clockwise.
USER INFORMATION
The maintenance message "after Hours run" is not possible with this
control unit.
+
+
GENERAL PARAM.
-10°C
Min outside temp
GENERAL PARAM.
no
maint. message
automatic
+
GENERAL PARAM.
Date
maint. message
automatic