12.2 Setting the temperature range
With this function you can set the upper limit for the required DHW temperature.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "DHW" appears.
Press "Display" to call up a submenu (here: "DHW").
The display shows the selected submenu.
Turn the rotary selector until submenu "Range to" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "80°C").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
WARNING!
RISK OF SCALDING
from hot water!
There is a risk of scalding if the required DHW temperature is set higher
than 60 °C.
z
In such cases, only ever draw off mixed water (hot and cold).
+
+
DHW DATA
yes
DHW
DHW DATA
60°C
Range to
+
DHW DATA
80°C
Range to
Input range
Factory setting
Range to
60 °C – 80 °C
60 °C