Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
65
11.21 Enter servomotor runtime
Here you may enter the servomotor runtime of existing servomotors. Generally,
servomotors have a runtime of 120 sec.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here: "Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
The display shows the selected submenu.
Turn the rotary selector until submenu "Servomotor runtime" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "90s").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
USER INFORMATION
If you notice a constant oscillation of the mixer, you can slow down the control
characteristics by reducing the servomotor runtime. Then the constant cycling
of the mixer will stop
.
+
+
HEAT CIRC. DATA 2
Radiators
Heating system
HEAT CIRC. DATA 2
120s
runtime
Servomotor
+
HEAT CIRC. DATA 2
90s
runtime
Servomotor
Input range
Factory setting
Servomotor runtime
10 seconds – 600 seconds
120 seconds