13.1 Setting the minimum heat-up temperature
This menu will only be displayed by the Logamatic 4323 control unit if address
0 or 1 has been selected. The heat consumers will only be supplied with heat if
the set temperature has been exceeded, or no later than after the time set up
under "Maximum Heat-up time" has expired.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Substation" appears.
The display shows the selected main menu.
Press "Display" to call up a submenu (here: "Minimum Heat-up temp.").
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "60°C").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
+
+
SERVICE LEVEL
Substation
Substation
50°C
Heat-up temp.
Minimum
+
Substation
60°C
Heat-up temp.
Minimum
USER INFORMATION
If "off" has been selected, any possibly installed buffer or the existing start-up
time of a heat source not regulated by the control unit will then not be taken into
consideration.
Input range
Factory setting
Minimum heat-up temp.
off
1 °C – 60 °C
50 °C