39
Table 16 – Thermistor Resistance vs Temperature
Values for Space Temperature Sensor, Supply Air
Temperature Sensor, and Outdoor Air Temperature
Sensor
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
---40
---40
335,651
---35
---31
242,195
---30
---22
176,683
---25
---13
130,243
---20
---4
96,974
---15
5
72,895
---10
14
55,298
---5
23
42,315
0
32
32,651
5
41
25,395
10
50
19,903
15
59
15,714
20
68
12,494
25
77
10,000
30
86
8,056
35
95
6,530
40
104
5,325
45
113
4,367
50
122
3,601
55
131
2,985
60
140
2,487
65
149
2,082
70
158
1,752
SUPPLY AIR
RETURN AIR
SUPPLY AIR
TEMPERATURE
SENSOR
ROOF
CURB
C08200
Fig. 44 -- Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
EconoMi$er 2
The RTU--MP control is used with EconoMi$er2 (option
or accessory) for outdoor air management. The damper
position is controlled directly by the RTU--MP control;
EconoMi$er 2 has no internal logic device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
S
Enthalpy control (outdoor air or differential sensors)
S
Space CO
2
sensor
S
Outdoor air CO
2
sensor
Field Connections -- Field connections for accessory
sensors and input devices are made the RTU--MP, at plugs
J1, J2, J4, J5, J11 and J20. All field control wiring that
connects to the RTU--MP must be routed through the
raceway built into the corner post as shown in Fig. 37.
The raceway provides the UL required clearance between
high-- and low--voltage wiring. Pass the control wires
through the hole provided in the corner post, then feed the
wires thorough the raceway to the RTU--MP. Connect to
the wires to the removable Phoenix connectors and then
reconnect the connectors to the board.
Space Temperature (SPT) Sensors
A field--supplied Bryant space temperature sensor is
required with the RTU--MP to monitor space temperature.
There are 3 sensors available for this application:
S
33ZCT55SPT, space temperature sensor with override
button
S
33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment
S
33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a
three--conductor shielded cable for the sensor and setpoint
adjustment connections. If the setpoint adjustment
(slidebar) is not required, then an unshielded, 18 or 20
gauge, two--conductor, twisted pair cable may be used.
Connect T--55
See Fig. 45 for typical T--55 internal connections. Connect
the T--55 SEN terminals to RTU--MP J20--1 and J20--2.
(See Fig. 46.)
2
3
4
5
6
1
SW1
SEN
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
C08201
Fig. 45 -- T--55 Space Temperature Sensor Wiring
580J
Summary of Contents for 580J*08--14D
Page 10: ...10 COOLING CHARGING CHARTS C09221 Fig 10 Cooling Charging Charts 08D F Both Circuits 580J ...
Page 11: ...11 COOLING CHARGING CHARTS C09222 Fig 11 Cooling Charging Charts 12D F Both Circuits 580J ...
Page 36: ...36 C07129 Fig 42 RTU MP Multi Protocol Control Board 580J ...
Page 37: ...37 C09163 Fig 43 Typical RTU MP System Control Wiring Diagram 580J ...
Page 60: ...60 C09156 Fig 73 580J Typical Unit Wiring Diagram Power 08D F 208 230 3 60 580J ...
Page 61: ...61 C09157 Fig 74 580J Typical Unit Wiring Diagram Control 08 12D F 208 230 3 60 580J ...
Page 84: ...84 580J ...