14
Table 1 – Cooling Service Analysis
PROBLEM
CAUSE
REMEDY
Compressor and Condenser
Fan Will Not Start.
Power failure.
Call power company.
Fuse blown or circuit breaker tripped.
Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
or control relay.
Replace component.
Insufficient line voltage.
Determine cause and correct.
Incorrect or faulty wiring.
Check wiring diagram and rewire correctly.
Thermostat setting too high.
Lower thermostat setting below room temperature.
Compressor Will Not Start But
Condenser Fan Runs.
Faulty wiring or loose connections in
compressor circuit.
Check wiring and repair or replace.
Compressor motor burned out, seized, or
internal overload open.
Determine cause. Replace compressor.
Defective run/start capacitor, overload, start
relay.
Determine cause and replace.
One leg of three---phase power dead.
Replace fuse or reset circuit breaker. Determine
cause.
Compressor Cycles (other
than normally satisfying
thermostat).
Refrigerant overcharge or undercharge.
Recover refrigerant, evacuate system, and recharge
to nameplate.
Defective compressor.
Replace and determine cause.
Insufficient line voltage.
Determine cause and correct.
Blocked condenser.
Determine cause and correct.
Defective run/start capacitor, overload, or start
relay.
Determine cause and replace.
Defective thermostat.
Replace thermostat.
Faulty condenser---fan motor or capacitor.
Replace.
Restriction in refrigerant system.
Locate restriction and remove.
Compressor Operates
Continuously.
Dirty air filter.
Replace filter.
Unit undersized for load.
Decrease load or increase unit size.
Thermostat set too low.
Reset thermostat.
Low refrigerant charge.
Locate leak; repair and recharge.
Leaking valves in compressor.
Replace compressor.
Air in system.
Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted.
Clean coil or remove restriction.
Excessive Head Pressure.
Dirty air filter.
Replace filter.
Dirty condenser coil.
Clean coil.
Refrigerant overcharged.
Recover excess refrigerant.
Air in system.
Recover refrigerant, evacuate system, and recharge.
Condenser air restricted or air short---cycling.
Determine cause and correct.
Head Pressure Too Low.
Low refrigerant charge.
Check for leaks; repair and recharge.
Compressor valves leaking.
Replace compressor.
Restriction in liquid tube.
Remove restriction.
Excessive Suction Pressure.
High head load.
Check for source and eliminate.
Compressor valves leaking.
Replace compressor.
Refrigerant overcharged.
Recover excess refrigerant.
Suction Pressure Too Low.
Dirty air filter.
Replace filter.
Low refrigerant charge.
Check for leaks; repair and recharge.
Metering device or low side restricted.
Remove source of restriction.
Insufficient evaporator airflow.
Increase air quantity. Check filter and replace if
necessary.
Temperature too low in conditioned area.
Reset thermostat.
Outdoor ambient below 25° F.
Install low---ambient kit.
Evaporator Fan Will Not Shut
Off.
Time off delay not finished.
Wait for 30---second off delay.
Compressor Makes Excessive
Noise.
Compressor rotating in wrong direction.
Reverse the 3---phase power leads.
580J
Summary of Contents for 580J*08--14D
Page 10: ...10 COOLING CHARGING CHARTS C09221 Fig 10 Cooling Charging Charts 08D F Both Circuits 580J ...
Page 11: ...11 COOLING CHARGING CHARTS C09222 Fig 11 Cooling Charging Charts 12D F Both Circuits 580J ...
Page 36: ...36 C07129 Fig 42 RTU MP Multi Protocol Control Board 580J ...
Page 37: ...37 C09163 Fig 43 Typical RTU MP System Control Wiring Diagram 580J ...
Page 60: ...60 C09156 Fig 73 580J Typical Unit Wiring Diagram Power 08D F 208 230 3 60 580J ...
Page 61: ...61 C09157 Fig 74 580J Typical Unit Wiring Diagram Control 08 12D F 208 230 3 60 580J ...
Page 84: ...84 580J ...