Page 88
Bradford White Corp.
Label
Description
How to Reach
Modbus
address
Each controller must have a unique Modbus
address.
<Home screen> Setup button <Setup
screen> Control setup button/ Change
address button
Number of
controllers in
Flap Valve
system
Each controller needs to know how many flap
valves are included in the whole system. On a
system with 4 boilers, there would be a total of 8
flap valves.
<Home screen> Select a controller
<Status Summary screen> Configure
button <Configuration Menu> Select Flap
Valve Configuration
Outdoor
temperature
source
This configures which source is used to provide
outdoor temperature data: S5 sensor, S10 sensor,
Enviracom sensor, or Modbus communication”
<Home screen> Select a controller
<Status Summary screen> Configure
button <Configuration Menu> Select
Sensor Configuration
System
pump cycle
count
System pump cycle count. Can be written to
a new value (e.g. if the pump or controller is
replaced).
<Home screen> Select a controller
<Status Summary screen> Configure
button <Configuration Menu> Select
Statistics Configuration
Temperature
units
This parameter determines whether temperature
is represented in units of Fahrenheit or Celsius
degrees.
<Home screen> Select a controller
<Status Summary screen> Configure
button <Configuration Menu> Select
System Configuration
Lead/
Lag Warm
Weather
Shutdown
Enable
When the Lead/Lag system is enabled, and this
feature is enabled, this feature will turn off the
whole system (for Central Heating functions)
when the outdoor temperature is warm enough.
This prevents the system from running when
there is no need for heat.
If Lead/Lag enabled –
<Home screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen> Advanced Settings button/ Left-
or Right- arrow buttons
Warm
weather
shutdown
setpoint
If the outdoor temperature is higher than this,
the system will be shut off for Central Heating
functions.
If Lead/Lag enabled –
Home screen/ View Lead/Lag button/
Lead/Lag screen/ Lead/Lag Master
button/ Lead/Lag Master screen/
Configure button/ Lead/Lag Master
Summary of Contents for BNTH1000
Page 2: ...Bradford White Corp...
Page 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Page 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Page 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Page 40: ...Page 36 Bradford White Corp...
Page 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Page 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Page 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Page 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Page 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Page 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Page 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Page 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Page 140: ...Page 136 Bradford White Corp This page intentionally left blank...