Page 18
Bradford White Corp.
Section 4
GaS SUPPly anD PIPInG
4.1
Gas Supply and Piping
Gas piping should be supported by suitable hangers
or floor stands, not the appliance.
Installers should refer to local building and safety
codes or, in the absence of such requirements, follow
the National Fuel Gas Code, ANSI Z223.1 NFPA 54
and/or CSA B149.1, Installation Codes.
Review the following instructions before proceeding
with the installation.
1. Verify that the appliance is fitted for the proper
type of gas by checking the rating plate. Brute
Elite will function properly without the use of
high altitude modification at elevations up to
10,000 feet (3050 m).
2. The maximum inlet gas pressure must not
exceed 13” W.C. (3.2 kPa). The minimum inlet
gas pressure is 4” W.C. (1.0 kPa).
3. Refer to Tables 6A, 6B, 6C and 6D to size the
piping.
4. Run the gas supply line in accordance with all
applicable codes.
5. Locate and install manual shutoff valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of
the gas controls.
7. All threaded joints should be coated with
piping compound resistant to the action of
liquefied petroleum gas.
8. The appliance and its individual shutoff valve
must be disconnected from the gas supply
piping during any pressure testing of that
system at test pressures in excess of 1/2 PSIG
(3.45 kPa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas
supply piping system at test pressures equal to
or less than 1/2 PSIG (3.45 kPa).
10. The appliance and its gas connection must be
leak tested before placing it in operation.
11. Purge all air from gas lines.
WarnInG
Open flame can cause gas to ignite and result in
property damage, severe injury, or loss of life.
note -
The Brute Elite appliance and all other gas
appliances sharing the gas supply line must be firing
at maximum capacity to properly measure the inlet
supply pressure. The pressure can be measured at
the supply pressure port on the gas valve. Low gas
pressure could be an indication of an undersized
gas meter, undersized gas supply lines and/or an
obstructed gas supply line. Some Brute Elite’s are
equipped with low and high gas pressure switches
that are integrally vent limited. These types of de-
vices do not require venting to atmosphere.
Summary of Contents for BNTH1000
Page 2: ...Bradford White Corp...
Page 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Page 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Page 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Page 40: ...Page 36 Bradford White Corp...
Page 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Page 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Page 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Page 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Page 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Page 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Page 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Page 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Page 140: ...Page 136 Bradford White Corp This page intentionally left blank...