Page 62
Bradford White Corp.
table 14 – number of Controls
Number of
boilers
Number of
controls
2
4
3
6
4
8
For example, if your system has three boilers,
there would be a total of six controllers (two
for each boiler), so you would enter “6” for
Number of Controls.
5. Press the line for Controller ID. Because you
are changing a parameter that is related to
safety, the system will present a warning that
looks like this:
fig. 72 – Parameter Safety Warning
Press OK to continue. The system will ask
you to login before you make a change.
Note that any changes you make will apply
only to one controller – the controller you
have already selected. If you want the same
change to apply to other controllers, you must
change each of them separately.
Once you change one of these safety-related
parameters, you must finish the verification
process, or the control system
will not let the
boiler operate
. Each control in a boiler must
be verified separately.
6. Press again on the line for Controller
ID. Table 15 shows how the Primary and
Secondary controls should be numbered for
each of the boilers.
In this example, we are still working with the
Primary control for Boiler 1. From the table,
you can see that this control should have a flap
valve ID of “1.” Enter the correct ID from
Table 5 in this field.
WarnInG
If the controller cannot find a signal from one
of the flap valves, the control system will act to
prevent backflow by energizing the blower of the
control with the bad flap valve. If this cannot be
done the control will not allow the whole system to
run. For this reason, it is important that all of the
flap valves be identified correctly.
7. Set the address for the other controller on this
boiler in the same way.
8. At this point, you have set the flap valve ID’s
for both controllers on this boiler. Before you
leave, you must finish the verification process,
or the control system will not let the boiler
operate.
Press the Back arrow to return to the
Configuration screen.
Fig. 73 – Configuration Screen
9. In a moment, you will need to reset the
controller by pressing a button on the front of
the unit. See Fig. 74. The controllers for the
two boilers are mounted behind the door on
the front of the unit.
Boiler 1
Boiler 2
Boiler 3
Boiler 4
Primary control
1
3
5
7
Secondary control
2
4
6
8
table 15 – flap Valve Controller ID addressing
Summary of Contents for BNTH1000
Page 2: ...Bradford White Corp...
Page 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Page 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Page 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Page 40: ...Page 36 Bradford White Corp...
Page 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Page 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Page 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Page 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Page 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Page 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Page 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Page 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Page 140: ...Page 136 Bradford White Corp This page intentionally left blank...