Page 84
Bradford White Corp.
Label
Description
How to Reach
CH (Central
Heat)
Setpoint
This setpoint is used when the time-of-day input
is off. If the outdoor reset function is active, this
setpoint provides one coordinate for the outdoor
reset curve. See the section for the CH Outdoor
Reset parameter.
If Lead/Lag enabled –
<Home screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen>
CH (Central
Heat) “Time
of Day”
Setpoint
This setpoint is used when the time-of-day input
is on. If the outdoor reset function is active,
this Setpoint provides one coordinate for the
shifted outdoor reset curve, because the time-
of-day switch is on. See the section for the CH
Outdoor Reset parameter.”
If Lead/Lag enabled –
<Home screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen>
DHW
(Domestic
Hot Water) D
Gain
This gain applied to the Differential term of the
PID equation for the DHW loop.
<Home screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration screen>
DHW
(Domestic
Hot Water)
Enable
This parameter determines whether the
Domestic Hot Water loop is enabled or disabled.
When it is disabled, the demand caused by the
DHW sensor is ignored. It may be disabled to
turn it off temporarily or because the application
does not use this feature.
<Home screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration screen>
DHW
(Domestic
Hot Water)
has priority
over CH
(Central
Heat)
This parameter determines the priority of
Domestic Hot Water vs. Central Heat call-for-
heat, when both of these are enabled and active.
(The DHW priority also may shift for a period
of time, as specified by DHW Priority time and
method parameters.)”
<Home screen> Lead Lag Master <Lead
Lag Master screen> Configure button
<Lead Lag Master Configuration screen>
Advanced Settings button/ Left- and
Right- arrow buttons <Domestic Hot
Water screen>
DHW
(Domestic
Hot Water) I
gain
This gain applied to the Integral term of the PID
equation for the DHW loop.
<Home screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration>
DHW
(Domestic
Hot Water)
off hysteresis
The off hysteresis is added to the Domestic Hot
Water Setpoint to determine the temperature at
which the DHW burner demand turns off.
<Home screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration screen>
DHW
(Domestic
Hot Water)
on hysteresis
The on hysteresis is subtracted from the
Domestic Hot Water Setpoint to determine the
temperature at which the DHW burner demand
turns on.
<Home screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration>
DHW
(Domestic
Hot Water) P
gain
This gain applied to the Proportional term of the
PID equation for the DHW loop.
<Home screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration screen>
DHW
(Domestic
Hot Water)
priority
override time
If this parameter is non-zero then a Domestic
Hot Water demand will shift its priority vs.
other demand sources according to the specified
time. The priority override timing is reset when
demand from the DHW source turns off.
<Home screen> Lead Lag Master button
<Lead Lag Master screen> Configure
button <Lead Lag Master Configuration
screen> Advanced Settings button
<Domestic Hot Water screen>
Summary of Contents for BNTH1000
Page 2: ...Bradford White Corp...
Page 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Page 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Page 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Page 40: ...Page 36 Bradford White Corp...
Page 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Page 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Page 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Page 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Page 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Page 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Page 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Page 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Page 140: ...Page 136 Bradford White Corp This page intentionally left blank...