Page 58
Bradford White Corp.
Job D - Disable the lead/lag master
function on the lead/lag Slaves
(This is an individual function – do this for each of the controls,
except the one used as the Lead/Lag Master. Use the separate
Operator Interface on each boiler.)
At the beginning of this section, we described
the Master and Slave arrangement used with the
Lead/Lag system. In the previous section, we
explained how to set up one controller as the Lead/
Lag Master. As we said, the controller used as the
Master (usually the Primary controller for Boiler 1)
also serves as a Slave (usually Slave 1). A single
controller performs both functions.
When the controllers arrive from the Bradford White
factory, they will all be configured as slaves. Your
job in this step is to disable the Lead/Lag Master
function on each of the controls, except for the one
control that will be used as the Lead/Lag Master –
usually the Primary control on Boiler 1.
1. From the Home screen (Fig. 59), press the
icon for the controller you want to work
with. In this example, we will start with the
Secondary controller for Boiler 1, and make
sure this is not set up as a Master.
fig. 59 – Home Screen
2. The system will take you to the Status
Summary screen.
fig. 60 – Status Summary Screen
3. To disable the Master function on this
controller, press the Configure button. Figure
61 shows the Configuration screen.
Fig. 61 – Configuration Screen
4. Scroll down through the list until you find the
line for LL Master Configuration. See Fig. 62.
Fig. 62 – Lead/Lag Master Configuration
Press on the line for Master Enable. The
system will go to a separate screen and ask
you to login using a password. Enter the
password (see Section 8.2), return to the
Master Configuration screen, then press the
line for Master Enable again. Change the
entry to Disabled.
Don’t change any of the other entries on this
screen.
5. At this point, you have disabled the Master
function on one of the controllers. You will
need to repeat the process for each of the other
controllers in the system (except the Primary
Controller on Boiler 1).
Go to the Operator Interface on the next boiler.
Repeat steps 1 through 4 for the first controller
on that boiler.
6. Repeat the steps listed above for each of the
other controllers on the system. Disable the
Master function on each of them.
Summary of Contents for BNTH1000
Page 2: ...Bradford White Corp...
Page 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Page 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Page 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Page 40: ...Page 36 Bradford White Corp...
Page 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Page 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Page 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Page 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Page 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Page 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Page 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Page 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Page 140: ...Page 136 Bradford White Corp This page intentionally left blank...