Page 16
Bradford White Corp.
When the unit is vented through the roof, the vent
must extend at least 3 feet (0.9 m) above the point at
which it penetrates the roof. It must extend at least
2 feet (0.6 m) higher than any portion of a building
within a horizontal distance of 10 feet (3.0 m), and
high enough above the roof line to prevent blockage
from snow. The vent terminal offered with the Brute
Elite can be used in both vertical and horizontal
applications. When the combustion air is taken from
the roof, the combustion air must terminate at least
12” (30 cm) below the vent terminal.
3.3.4 Vertical Combustion air terminal
When combustion air is taken from the roof, a field-
supplied rain cap or an elbow arrangement must be
used to prevent entry of rain water. The opening on
the end of the terminal must be at least 12” (30 cm)
above the point at which it penetrates the roof, and
high enough above the roof line to prevent blockage
from snow. When the vent terminates on the roof, the
combustion air must terminate at least 12” (30 cm)
below the vent terminal.
3.3.5 Installations in the Commonwealth
of massachusetts
In Massachusetts the following items are required
if the side-wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of
the venting, including but not limited to decks and
porches. (From Massachusetts Rules and regulations
248 CMR 5.08.)
1.
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall vented
gas fueled appliance, the installing plumber or
gas-fitter shall observe that a hard-wired carbon
monoxide detector with an alarm battery back-up
is installed on the floor level where the gas appli
-
ance is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery
operated or hard-wired carbon monoxide detec-
tor with an alarm is installed on each additional
level of the dwelling, building or structure served
by the side-wall horizontally vented gas fueled
equipment. It shall be the responsibility of the
property owner to secure the services of qualified
licensed professionals for installation of hard-
wired carbon monoxide detectors.
a. In the event that the side-wall horizontally
vented gas fueled equipment is installed in a
crawl space or an attic, the hard-wired carbon
monoxide with alarm and battery back-up may
be installed on the next adjacent floor level.
b. In the event that the requirements of the sub-
division cannot be met at the time of completion
of installation, the owner shall have a period of
thirty (30) days to comply with the above re-
quirements, provided, however, that during said
thirty (30) day period, a battery operated carbon
monoxide detector with an alarm be installed.
2.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector shall comply
with NFPA 720 and be ANSI/UL 2034 listed
and IAS certified.
3.
Signage
A metal or plastic identification plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust
vent terminal for horizontally vented gas fueled
heating appliance or equipment. The sign shall
read, in print no less than one-half (1/2) inch in
size: “GAS VENT DIRECTLY BELOW, KEEP
CLEAR OF ALL OBSTRUCTIONS.”
4.
Inspection
The state or local gas inspector of the side-wall
horizontally vented gas fueled appliance shall
not approve the installation unless, upon inspec-
tion, the inspector observes carbon monoxide
detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a) 1-4.
3.4
Common Vent test
note -
This section does not describe a method
for common venting Brute Elite’s. It describes
what must be done when a unit is removed from a
common vent system. Brute Elite’s require special
vent systems and fans for common vent. Contact
the factory if you have questions about common
venting Brute Elite’s.
When an existing boiler is removed from a common
venting system, the common venting system is
likely to be too large for proper venting of the
appliances remaining connected to it.
At the time of removal of an existing boiler,
the following steps shall be followed with each
appliance remaining connected to the common
venting system placed in operation, while the other
appliances remaining connected to the common
venting system are not in operation.
1. Seal any unused openings in the common
venting system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion or
other deficiencies which could cause an unsafe
Summary of Contents for BNTH1000
Page 2: ...Bradford White Corp...
Page 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Page 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Page 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Page 40: ...Page 36 Bradford White Corp...
Page 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Page 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Page 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Page 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Page 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Page 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Page 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Page 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Page 140: ...Page 136 Bradford White Corp This page intentionally left blank...