Page 59
Brute Elite Boilers and Water Heaters
Job e – Set Up the modbus Control
addressing
(This is an individual function – do this for each of the controls
Use the separate Operator Interface on each boiler.)
Do this on any system with multiple boilers.
note
– Do not connect the Modbus wiring yet. The
controls must be set up and addressed correctly
before the wiring is complete. If the wiring is
attached before the control Modbus addresses are
changed, there will be multiple controls with the
same address, and the system will not work.
1. When the system is operating under the
control of the Lead/Lag system, the Lead/Lag
Master needs a way to identify each controller
in each of the boilers. On a system with four
boilers there will be eight separate controllers.
You will need to give each of these controllers
a unique Modbus address. (Notice that this is
different from the name of the controller. We
set the controller names in a previous step.)
2. Power up all of the boilers in the system. It
will take a minute for each Operator Interface
to “synchronize” with its two controllers.
3. Start at the Home screen on the first boiler.
See Fig. 63.
fig. 63 – Home Screen
4. Press the Setup button in the lower right-hand
corner to go to the Setup screen.
fig. 64 – Setup Screen
5. Press the Control Setup button. Figure 65
shows the Control Setup screen.
fig. 65 – Control Setup Screen
6. The first number on each line (01, 02, etc.) is
the Modbus control address. Let’s set up the
Modbus address for the first controller in the
line - the Primary controller on Boiler 1. Press
the top line – Brute Elite Primary.
7. Press the Change Address button. You need to
know the installer-level password to change
the address, so the system will ask you to log
in. (For more information on the passwords
and logging in, see the section on “Using the
Touchscreen.”) Press the padlock symbol in
the upper right-hand corner of the screen, then
type in the installer-level password and press
the OK button.
8. Press the Change Address button again. The
system will present a screen that lets you
change the address.
fig. 66 – Changing modbus address
9. Table 13 shows how the Modbus control
addressing should be set up. The system is
simple, but it is important to only use the
correct address listed in the table. Do not
use any other address than the one listed in
the table for the control you are addressing.
In this example, the correct address for the
Summary of Contents for BNTH1000
Page 2: ...Bradford White Corp...
Page 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Page 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Page 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Page 40: ...Page 36 Bradford White Corp...
Page 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Page 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Page 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Page 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Page 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Page 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Page 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Page 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Page 140: ...Page 136 Bradford White Corp This page intentionally left blank...