Security Escort
System wiring | en
47
Robert Bosch (SEA) Pte Ltd
Training Manual
2017.08 | V2.18.1.0 | DOC
2.
Set up and configure the IP address of the Moxa device. There are several methods to
configure the IP address. Please refer to the Moxa User Manual on steps to configure the
IP address.
3.
From a computer on the Ethernet network, login to the Moxa device using the web
browser interface.
4.
Go to
Serial Settings
>
Port 1
. Remove any entry in the
Port alias
field (it must be
empty). Set the
Baud Rate
field as “9600”, the
Data Bits
field as “8”, the
Stop Bits
field
as “1”, the
Parity
field as “None”, the
Flow Control
field as “None”, the
FIFO
field as
“Enable” and the
Interface
field as “RS-232”.
5.
Click the
[Submit]
button to make the changes and restart the Moxa device.
6.
Go to
Operating Settings
>
Port 1
. It is recommended (depending on the setup
environment) to enter “1” in the
TCP alive check time
field, “0” in the
Inactivity time
field, and “0” in the
Force transmit
field. Please refer to the Moxa User Manual for further
details. Enter the port number of the transponder in the
Local TCP Port
field. This port