Security Escort
System menus and dialogs | en
199
Robert Bosch (SEA) Pte Ltd
Training Manual
2017.08 | V2.18.1.0 | DOC
RF point troubles
Output all reported radio frequency communication of receiver
and alert unit troubles. Typically this item would be checked for
devices used to monitor problems.
Transponder maps
Outputs all transponder status maps. This selection is only used
for diagnostics. Leave this item unchecked.
Receive level maps
Outputs all maintenance alarm receive level maps. This selection
is only used for diagnostics. Leave this item unchecked.
Database errors
Outputs all reported database errors. This item is checked.
Transponder troubles
Outputs all reported transponder troubles. This item is checked
for devices used to monitor problems.
Point troubles
Outputs all reported receiver and alert unit troubles. This item is
checked for devices used to monitor problems.
Login changes
Reports all new system operator login and logout activity.
Network communications
Records all communications between networked computers.
This selection is only used for engineering diagnostics. Leaving
this item selected, generates a significant amount of history and
fills up the hard disk drive very quickly and may bog down the
system during high traffic times. Always leave this item
unchecked.
Modem communications
Records all communications to the modem for remote
communications and pager access. This selection is only used for
diagnosing pager communication problems. Leave this item
unchecked.
Analyze alarms
This option outputs data allowing an engineer to evaluate how
well the location algorithm is performing. Leave this item
unchecked.
Master computer switch
Records when the master and slave computers switch roles.
Transponder data view
Allows the data created by the
Transponder Data View
screen to
be output. This selection is only used for engineering
diagnostics. Leave this item unchecked.
Printer output
Allows the data being sent to the printer to be sent to other
outputs. This item is unchecked.
8.3.3
Popup trouble filter
The Security Escort System contains many built-in self testing features. Each transponder
tests the condition of the receivers and alert units connected to it.
When the transponder finds a device reporting a trouble condition, it communicates the
problem and the device identity to the Central Console. This generates a brief alert tone,
displays a pop-up message for the operator, and sends an optional pager message. The
message indicates the nature of the trouble and instructs the operator on the proper course of
action. The event is recorded on the hard disks of both the main and backup computers and
on the printout.
The status of the device is recorded in the
Transponder Current Status
menu item under the
Setup