196
en | Points
Control Panel
2017.03 | 09 | F.01U.303.998
Program Entry Guide
Bosch Security Systems, Inc.
RPS Menu Location
Points > Point Indexes > Disable Restorals
10.3.19
Force Arm Returnable
Default
: No
Selections
:
–
Yes This point automatically returns to the system when it restores to normal.
–
No This point stays out of the system until the area is disarmed.
Use this parameter to allow points which were force armed out of the area to return back to
the armed state once they are normal again without needing to disarm the system.
Use this parameter on points assigned to loading dock doors that are required to be left open
until loading is completed. Once the loading dock door is closed, it detects an opening and
sends an alarm.
RPS Menu Location
Points > Point Indexes > Force Arm Returnable
10.3.20
Bypass Returnable
Default
: No
Selections
:
–
Yes This point automatically returns to the system when the area is disarmed.
–
No This point stays out of the system through arming and disarming cycles.
Use this parameter to return a point which has been bypassed, force armed or swinger
bypassed back into the system once the area this point is assigned to is disarmed.
Set this parameter to No for interlock points.
When not allowed to return to the system through disarming, the point must be manually
unbypassed using the UNBYPASS?, keypad function, Sked functions Unbypass a Point, or
Unbypass All Points, or remotely using RPS. For force armed points to remain bypassed,
ensure Force Arm Returnable, page 196 is set to No.
RPS Menu Location
Points > Point Indexes > Bypass Returnable
10.3.21
Bypassable
Default
:
–
Point Profiles 1 to 7-13, 20, 25-63: Yes
–
Point Profiles 2-6, 14-19, 21-24: No
Selections
:
–
Yes. This point can be bypassed and force armed.
–
No. This point can not be bypassed or force armed from the keypad or RPS. However, it
can be force armed by automatic arming at the end of the closing window (Refer to Auto
Close ), or by a Sked programmed to arm the area.
Use this parameter to allow this point to be bypassed and/or force armed.
When a 24-hour point or 24-hour supervisory point is bypassed, 24 HOUR BYPASS
continuously scrolls on the keypad. FIRE BYPASS scrolls to indicate a 24-hour fire point or a
fire supervisory point is bypassed. GAS BYPASS scrolls to indicate a gas detector or gas
supervisory point is bypassed.
To have the alarm capability of a 24-hour point without the continuous scrolling, use a
perimeter point with a Point Response, page 184 of 9 to E.
Summary of Contents for B8512G
Page 1: ...Control Panel B9512G B8512G B9512G E B8512G E en Program Entry Guide ...
Page 2: ......
Page 283: ......