Control Panel
User Configuration | en
151
Bosch Security Systems, Inc.
Program Entry Guide
2017.03 | 09 | F.01U.303.998
The armed states include:
–
Disarmed
–
All On delay armed
–
All On instant armed
–
Part On instant armed
–
Part On delay armed
All area types (Master, Associate, Regular and Shared) can be viewed using this function.
RPS Menu Location
User Configuration > User Keypad Functions > View Area Status
9.3.7
View/Delete Event Memory
Default
: E
Selections
: - , E, P
–
Disable (-) - Disable this function panel wide regardless of the user's authority level.
–
Enable (E) - Enable this function panel wide without requiring a passcode.
–
Passcode (P) - Require a passcode to enable this function panel wide.
This function allows the user to view and clear event memory. Event memory is not cleared
until the area is re-armed.
RPS Menu Location
User Configuration > User Keypad Functions > View/Clear Event Memory
9.3.8
View Point Status
Default
: E
Selections
: - , E, P
–
Disable (-) - Disable this function panel wide regardless of the user's authority level.
–
Enable (E) - Enable this function panel wide without requiring a passcode.
–
Passcode (P) - Require a passcode to enable this function panel wide.
This function allows the user to view point status, point text and the electrical state (normal,
open, short and missing) of each point assigned to the area.
RPS Menu Location
User Configuration > User Keypad Functions > View Point Status
9.3.9
Walk Test (all Non-Fire Burg Points)
Default
: E
Selections
: - , E, P
–
Disable (-) - Disable this function panel wide regardless of the user's authority level.
–
Enable (E) - Enable this function panel wide without requiring a passcode.
–
Passcode (P) - Require a passcode to enable this function panel wide.
This function allows the user to test controlled points in areas within the keypad's scope
without sending reports to the central station.
24 hour points cannot be tested using this walk test mode.
RPS Menu Location
User Configuration > User Keypad Functions > Walk Test (All Non-Fire Burg Points)
9.3.10
Walk Test All Fire Points
Default
: P
Selections
: - , E, P
–
Disable (-) - Disable this function panel wide regardless of the user's authority level.
–
Enable (E) - Enable this function panel wide without requiring a passcode.
–
Passcode (P) - Require a passcode to enable this function panel wide.
Summary of Contents for B8512G
Page 1: ...Control Panel B9512G B8512G B9512G E B8512G E en Program Entry Guide ...
Page 2: ......
Page 283: ......