Control Panel
User Configuration | en
159
Bosch Security Systems, Inc.
Program Entry Guide
2017.03 | 09 | F.01U.303.998
Duress Disarm Profile
User Authority Level 14 is programmed by default as a Duress disarm profile. When Duress
Type is set to 3, the SIA CP-01 compliant Duress Passcode feature is enabled. Duress Types 1
and 2 are not allowed in SIA CP-01 compliant installations.
With Authority Level 14 assigned to a user passcode in an area, that user has the authority to
disarm and send a Duress event from that area.
All Duress-capable passcodes must be unique and cannot be derived from other passcodes.
To facilitate this uniqueness, User Authority Level 14 is pre-programmed from the factory as
an example of Duress Disarm authority.
A Duress Disarm user authority level requires the following functions to be enabled:
–
Disarm Select, page 158
–
Send Duress, page 171
–
Disarm by Passcode, page 172
RPS Menu Location
User Configuration > Authority Levels > Disarm Select
9.4.4
All On, Delay
Default:
Authority Levels 1-5: Enabled (E)
Authority Levels 6-15: Blank (-)
Selections:
–
Blank (-): This function is not authorized for the user who is assigned this authority level.
–
Enabled (E): This function is authorized for the user who is assigned this authority level.
This parameter allows users to turn the system All On, Delay (arm all Part On (perimeter) and
Interior points with exit and entry delay time in areas within the scope of the keypad being
used, and that correspond to the user's Authority Level).
If a user uses Command 1, All On, Delay only arms the area the keypad is assigned to.
If a user uses the Remote Security Control app (RSC) to turn the system All On, Delay, the
areas that correspond to the user’s Authority Level are armed.
RPS Menu Location
User Configuration > Authority Levels > All On Delay
9.4.5
All On, Instant
Default:
Authority Levels 1 & 2: Enabled (E)
Authority Levels 3-15: Blank (-)
Selections:
–
Blank (-): This function is not authorized for the user who is assigned this authority level.
–
Enabled (E): This function is authorized for the user who is assigned this authority level.
This parameter allows users to turn the system All On, Instant (arm all Part On (perimeter)
and Interior points with no exit and no entry delay time in areas within the scope of the
keypad being used, and that correspond to the user's Authority Level).
If a user uses Command 11, All On, Instant only arms the area the keypad is assigned to.
If a user uses the Remote Security Control app (RSC) to turn the system All On, Instant, the
areas that correspond to the user’s Authority Level are armed.
RPS Menu Location
User Configuration > Authority Levels > All On Instant