Control Panel
Keypads | en
121
Bosch Security Systems, Inc.
Program Entry Guide
2017.03 | 09 | F.01U.303.998
Notice!
SDI2 keypads are always supervised regardless of this parameter's setting.
Notice!
Keypads sharing the same address setting display the same text and sound the same tones
regardless of which keypad keys are being pressed.
Notice!
TROUBLE SDI # reports are always reported as Area 1, Account 1 events regardless to which
area the SDI device is assigned.
Notice!
When this parameter is set to Yes, you cannot have duplicate DIP switch settings.
RPS Menu Location
Keypads > Keypad Assignments > Supervision
5.1.34
D125X Passcode [Esc] Option
Default
: Yes
Selections
:
–
Yes - entering a user passcode followed by the [Esc] key performs the legacy D125x
sequence. If bells are sounding alarms, the alarms are acknowledged. If no bells are
sounding and either silence or clear operations are allowed, the clear display task is
executed.
–
No - pressing the [Esc] key erases the last digit and if no digits are entered the task is
exited.
Notice!
This option is only available on D-Series D125x keypads from the Idle task only.
Notice!
Only available when "D125xRB Fire Keypad (SDI)" or the "D1255 VFD keypad (SDI)" is
selected as the Keypad Type, page 110.
RPS Menu Location
Keypads > Keypad Assignments > D125X Passcode [ESC] Option
5.2
Global Keypad Settings
5.2.1
A key Response
Default
: No Response
Selections
:
–
No Response (Invalid key press response)
–
Manual Fire Alarm (When A key and 1 key are held together for 2 sec.)
Summary of Contents for B8512G