Control Panel
Panel Wide Parameters | en
67
Bosch Security Systems, Inc.
Program Entry Guide
2017.03 | 09 | F.01U.303.998
This parameter determines how many times the control panel will re-send the heartbeat event
before declaring a Path Failure for a given SDI2 Destination.
An event is defined by the following device and destination combinations.
Device
Destination 1
Destination 2
Destination 3
Destination 4
SDI2-1
11
21
31
41
Onboard
Ethernet
10
20
30
40
Onboard Cellular 18
28
38
48
RPS Menu Location
Panel Wide Parameters > Enhanced Communications > Retry Count
3.11.8
AES Key Size
Default
: No Encryption
Selections
:
–
No Encryption
–
128 bit key length is 16 bytes.
–
192 bit key length is 24 bytes.
–
256 bit key length is 32 bytes.
This parameter identifies the AES key size.
RPS Menu Location:
Panel Wide Parameters > Enhanced Communications > AES Key Size
3.11.9
AES Encryption Key
Default
: <Default> (not encrypted)
Selections
: Thirty-two hexadecimal characters represented by an ID (01 to 100).
This parameter allows each receiver destination to be configured with a unique AES
encryption key.
The AES Encryption Key is based on AES Key Size, page 67. For the encryption key
configuration, only Key ID & Name is displayed.
By default RPS sets the AES Key string to <Default>. RPS validates if two or more network
destinations have the same network address. If yes, then RPS notifies the user to use the
same encryption key for those network destinations.
AES key strings are configured in Config >> System >> Encryption Key Tab
RPS Menu Location
Panel Wide Parameters > Enhanced Communications > AES Encryption Key
3.12
SDI2 RPS / Enhanced Communication
3.12.1
Enable Enhanced Communication?
Default
: Yes
Selections
:
–
Yes - enables reporting using an IP communicator (onboard, plug-in cellular, or SDI2).
–
No - disables reporting using an IP communicator.
To enable reporting using an IP communicator (onboard, plug-in cellular, or SDI2), set this
parameter to Yes, and set the Primary Destination Device, page 59 or Backup Destination Device,
page 60 for at least one Route Group to an Onboard IP, Plug-in Cellular, or SDI2 device.
Summary of Contents for B8512G