Function level
Custom function activation
C (armed and disarmed)
User token activates the custom function
assigned to the door controller only when the
entry area for the door controller regardless
of the armed state of the entry area.
Blank
User token does not activate the custom
function assigned to the door controller.
RPS Menu Location
Access > Doors > Custom Function #
12.1.7
Door Point
Default
: 0
Use this parameter to assign a point to a door. This point cannot be used for any other point
assignments.
Door Points must be programmed as Part On points. If a Door Point requires 24 hour point
type behavior, use the Part On point type with a Point Response of 9 to C for instant alarm
response when the area is on (armed) or off (disarmed).
If you select an on-board point (points 1-8) as a Door Point, be sure there is no EOL resistor
connected to the sensor loop on the control panel.
RPS Menu Location
Access > Doors > Door Point
See also
–
Debounce, page 178
12.1.8
Door Point Debounce
Default
: 600 ms
Selections
:
Debounce
300 ms
1800 ms
3300 ms
600 ms
2100 ms
3600 ms
900 ms
2400 ms
3900 ms
1200 ms
2700 ms
4200 ms
1500 ms
3000 ms
4500 ms
Notice!
Door Point Debounce parameter for Access Control Modules connected to SDI2 only
This parameter configures door point debounce for access control modules (B901) connected
to the SDI2 or SDx bus configured for SDI2 only.
Notice!
For Access Control Modules connected to SDI bus set point Debounce to 1.64
When the access control module (B901, or D9210C) is connected to the SDx bus configured
for SDI, set the point Debounce parameter to 1.64 seconds (Debounce, page 178).