Example 4
Reading parameter
Fixed Frequency 1
480 (type: long) in data set 3 with the current
parameter value -10.00 Hz.
Index = 480 + 0x2000 = 0x21E0, value = -1000 = 0xFFFFFC18
Client
Server
SDO Upload (expedited)
0
1
2
3
4
5
6
7
COB ID Control byte
Index
Subindex
Data
0x601
0x40
0xE0
0x21
0x03
--
--
--
--
Server
Client
Upload Response
0
1
2
3
4
5
6
7
COB ID Control byte
Index
Subindex
Data
0x581
0x43
0xE0
0x21
0x03
0x18
0xFC
0xFF
0xFF
If an error occurs during the reading process, the corresponding error code is given in
Bytes 4 … 7. Check chapter 11.3.3 for the error code list for SDO abort.
12.3.1.4
Example to Write parameters via Segmented Transfer
Write Parameter
User Name
029 (Type String), in data set 0 with the parameter val-
ue “Bonfiglioli Vectron CANopen” (= 27 characters = 0x1B characters).
Index = 29 + 0x2000 = 0x201D
ASCII
B
o
n
f
i
g
l
Hexadec-
imal
0x42
0x6F
0x6E
0x66
0x69
0x67
0x6C
ASCII
i
o
l
i
(blank)
V
e
Hexadec-
imal
0x69
0x6F
0x6C
0x69
0x20
0x56
0x65
ASCII
c
t
r
o
n
(blank)
C
Hexadec-
imal
0x63
0x74
0x72
0x6F
0x6E
0x20
0x43
ASCII
A
N
o
p
e
n
Hexadec-
imal
0x41
0x4E
0x6F
0x70
0x65
0x6E
Initiate Se-
quence
Client
Server
SDO Initiate Download Request (segmented)
0
1
2
3
4
5
6
7
COB ID Control byte
Index
Sub-index
Daten
0x601
0x21
0x1D
0x20
0x00
1B
00
00
00
Server
Client
Initiate Download Response (response: 9 bytes to be send)
0
1
2
3
4
5
6
7
COB ID Control byte
Index
Sub-index
Daten
0x581
0x60
0x1D
0x20
0x00
0x00
0x00
0x00
0x00
04/13
CM-CAN ACU
79
Summary of Contents for Vectron Active Cube
Page 1: ...ACTIVE CUBE CANopen Communication module CM CAN Frequency inverter 230 V 400 V...
Page 2: ......
Page 239: ......