8.6.2 Checking the Bus Termination
As mentioned in section 7.9 "Installation of the Bus", the bus must be
terminated at both ends. Check both car bus and group bus to make
sure that they have properly terminated ends.
INFO
!
Some types of position systems always terminate the can bus. In
such case, the termination on the CLK-03 has to be deactivated with
the DIP switch. You can find information on terminating devices in
their accompanying manuals or online at
www.CANopen-Lift.org
8.6.3 Checking the CAN Parameters
To check the CAN parameters of the control unit, call up the setup
information or the setup menu of the control unit. In PARAMETERS
→ TERMINALS → TERMINALS CAN1/2 you can find a list of all con-
nected CAN devices. Check if the devices that are to be used in your
system have been activated
.
As all CAN devices are pre-configured upon delivery of the control
unit, you need not set further parameters at this point. If you combine
a control system from OEM components, you may optionally pur-
chase a USB CAN adapter for the PC and CANwizard
®
« software for
parametrising the CAN devices. You can, however, also configure the
input and output terminals on the control display. Learn more about
CANwizard
®
and the configuration of devices in the CANwizard
manual and at
www.CANwizard.de
.
If all devices have given correct feedback, you can start the first
travel with emergency controls.
8.6.4 Checking the DCP Connection
If the inverter is selected via a DCP interface, the following items are
to be checked:
Does the wiring comply with the circuit diagrams,
Has bp308 been set to the correct drive/inverter type,
Has the DCP interface been activated in bp308 and in the inverter,
Have both units (control and drive) been set to the same protocol
(DCP3/DCP4+),
Are there no malfunctions at present.
90
Installation Manual System »bp308« – Commissioning Instructions
Fig. 56
A CLK unit correctly booted up
connected at the CAN-bus.
Fig. 57
Example of a IXXAT USB to
CAN adapter used for configur-
ing CAN components.
Summary of Contents for bp308
Page 14: ...15...
Page 15: ...16 Installation Manual System bp308 Product Certifications...
Page 54: ...55 Fig 31 Interference suppression circuit diagrams...
Page 114: ...Appendix A Menu Navigation bp308 Version 88D2312 29 08 2013 116...
Page 115: ...117...
Page 150: ...152...
Page 154: ......