1
KAPPA V 2001 water chiller
KAPPA V 2001 water chiller
KAPPA V 2001 water chiller
KAPPA V 2001 water chiller
KAPPA V 2001 water chiller
UNIT FRAME
UNIT FRAME
UNIT FRAME
UNIT FRAME
UNIT FRAME
Self-supporting frame made from galvanised steel protected with polyester powder paint enamel (stoved at 180°)
for resistance to atmospheric agents. Stainless steel screws and bolts.
COMPRESSORS
screw-type semi-hermetic compressor, direct male rotor/female rotor drive, with crankcase heater. Lubrification
ensured by delivery and intake pressure difference.
Continuous cooling capacity control available, enabling to maximise the energetic efficiency of the unit in any
working condition.
Integral electronic motor protection and temperature sensors inserted directly in windings.
Delta-star motor start-up and standard capacity step reduction.
CONDENSERS
CONDENSERS
CONDENSERS
CONDENSERS
CONDENSERS
Feature tube bundle coils made of copper tubes and high-efficiency aluminium fins. The use of V condensing coils
enables to reduce the unit dimensions, as well as to increase the air suction surface.
F A N S
F A N S
F A N S
F A N S
F A N S
Axial fans featuring sickle-shaped vane and conveyer designed to reduce noise emissions, directly driven by 6-
pole three-phase electric motor with integrated klixon thermal overload protection. IP 54 motor protection grading.
Fitted with safety fan guard.
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
EVAPORATOR
AISI 316 stainless steel braze-welded plate type. The use of plate-type exchangers enables to:
- reduce the amount of refrigerant fluid in the cicuit
- reduce the weight of the unit
- make maintenance easier
- reach higher COP/EER ratios
Insulated with closed-cell foam material for reduced heat loss.
All evaporators are fitted with temperature probe for anti-freeze protection.
REFRIGERANT CIRCUIT
REFRIGERANT CIRCUIT
REFRIGERANT CIRCUIT
REFRIGERANT CIRCUIT
REFRIGERANT CIRCUIT
Includes: compressor delivery valves, liquid line shut-off valve, charging connection, liquid sight glass, drier filter,
thermostatic valve, high and low pressure gauges, evaporation and condensation temperature readout by control.
ELECTRICAL PANEL
ELECTRICAL PANEL
ELECTRICAL PANEL
ELECTRICAL PANEL
ELECTRICAL PANEL
IP 54 category includes:
- main switch
- power cicuit automatic circuit breakers and fuses
- compressor contactors
- fan contactors
- microprocessor for control of the following functions:
- water temperature control
- anti-freeze protection
- compressor operation timing
- compressor automatic start-up sequence
- alarm signals
- alarm reset
- potential contact for remote alarm signals
- digital display of:
- inlet and outlet water temperature
- temperature and differential settings
- alarm description
- hour meters readout of operation and number of unit, compressor and pump (if present) start-ups
- high and low pressures, relative condensation and evaporation temperature controls.
Summary of Contents for KAPPA V 2001