25
4.9.4 “LE” VERSIONS - ELECTRICAL CONNECTIONS
4.9.4 “LE” VERSIONS - ELECTRICAL CONNECTIONS
4.9.4 “LE” VERSIONS - ELECTRICAL CONNECTIONS
4.9.4 “LE” VERSIONS - ELECTRICAL CONNECTIONS
4.9.4 “LE” VERSIONS - ELECTRICAL CONNECTIONS
“LE” versions are not provided with electronic controls. It is therefore necessary to provide the machine with an
external control or thermostat and connect it to the terminal board according to instructions contained in the
electrical diagrams supplied with the unit.
TABLE I - CONNECTION PIPE DIAMENTERS FOR “LE” VERSIONS
TABLE I - CONNECTION PIPE DIAMENTERS FOR “LE” VERSIONS
TABLE I - CONNECTION PIPE DIAMENTERS FOR “LE” VERSIONS
TABLE I - CONNECTION PIPE DIAMENTERS FOR “LE” VERSIONS
TABLE I - CONNECTION PIPE DIAMENTERS FOR “LE” VERSIONS
Distance [m]
MODEL
Suction
Liquid
Suction
Liquid
Suction
Liquid
KAP P A V
2001
[mm]
[mm]
[mm]
[mm]
[mm]
[mm]
16. 1
67
28
76
35
76
35
18. 1
76
35
76
35
90
42
23. 1
76
35
90
42
90
42
27. 1
76
42
90
42
90
42
32. 2
2x67
2x28
2x76
2x35
2x76
2x35
37. 2
2x76
2x35
2x76
2x35
2x90
2x42
41. 2
2x76
2x35
1x76
1x35
2x90
2x42
1x90
1x42
46. 2
2x76
2x35
2x90
2x42
2x90
2x42
50. 2
2x76
1x35
2x90
2x42
2x90
2x42
1x42
55. 2
2x76
2x42
2x90
2x42
2x90
2x42
30
10
20
Summary of Contents for KAPPA V 2001