52
PROBLEM
OPERATING MODE
PROBABLE CAUSE
REMEDY
COOLING
HEATING
I)
Frost on refrigerant
⊗
Liquid valve partially closed. Open valve fully.
circuit pipes.
⊗
Refrigerant filter clogged.
Replace filter cartridge.
L)
Unit functions without
⊗
⊗
Insufficient refrigerant.
See point G.
stopping.
⊗
⊗
Incorrect working set point Check set point
⊗
⊗
Excessive thermal capacity.
Reduce thermal capacity.
⊗
⊗
Compressor does not
deliver rated cooling power.
Check / replace / overhaul.
⊗
⊗
Refrigerant filter clogged.
Clean / replace.
M)
Unit operating normally
but with
⊗
⊗
Insufficient refrigerant
charge.
See point G.
insufficient power
⊗
⊗
Humidity in refrigerant
circuit.
Replace / dry filter and
recharge circuit.
⊗
4-way inversion valve de-
excited.
Check power supply and valve
windings / replace valve.