USER MANUAL 1.10 | DC1000 DIALOG-CONTROLLER
Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com
2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx
115
Digital output data
Module data
Type of outputs
Semiconductor, non-storing
Protection circuit for inductive
loads
Fast de-excitation
41 V terminal voltage (typ.) 24 V
Power loss due to de-excitation
max. 0.5 W / output
max. 4 W / module
Status display
Yes, green LED per input on the plug-in connector.
Overload protection
Yes, under thermal overload.
Short circuit protection
1) 2) 3)
Response threshold
Yes, electronic current limitation,
typ. 3 A.
1) Current is limited electronically. Triggering the short circuit protection causes thermal overload and the
thermal overload protection is tripped.
2) Starting from cold, maximally 10,000 permissible short circuits.
3) Total duration of the short circuits max. 500 hours.
Output delay
at „0“ after „1“
at „1“ after „0“
typ. 1 ms
typ. 1 ms
Output capacity
< 20 nF
Rated voltage
Voltage drop
(with rated current)
DC +24 V
< 0.1 V
Rated current with ‘1’ signal
0.5 A
Total current of all outputs
max. 2 A
Two outputs switched in parallel
for logic link
for increased output
permissible
permissible up to 1 A