USER MANUAL 1.10 | DC1000 DIALOG-CONTROLLER
Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com
DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx
42
2.7.4. DC1012 Panel cutout
CAUTION
Installation instruction:
Only install the Dialog-Controller on a level surface!
The support points on the Dialog-Controller may not deviate from one another
by more than +/-0.5 mm. If the Dialog-Controller is nonetheless mounted on a
base which is not level, mechanical tension can result in cracks in the front
panel!
The Dialog-Controller is intended for front installation. A square panel cutout is required. The support mate-
rial thickness may not exceed 6 mm. The panel cutouts are identical for units equipped with either a key-
board or a touch panel.
2VF100271DG00.cdr
2.7.5. Mounting regulation DC1012
The Dialog-Controllers are designed for automatic convection cooling.
The Dialog-Controllers must be mounted vertically onto a metallic mounting plate.
WARNING
Danger of overheating and fire!
The Dialog-Controller may be destroyed even at a permissible ambient tem-
perature if the convection cooling cannot function because it is built-in.
It must therefore be installed vertically and the upper and lower housing aper-
tures must not be covered over!
DANGER OF
OVERHEATING
AND FIRE!
Vertical
installation
Alle Maße in [mm] / All dimensions in [mm]
Frontansicht
Front view
4
0
-136
-272
-276
-4
0
2
6
2
0
6
3
4
6
3
8
6
4
1
2
4
1
6
Bohrungen /
5 mm (8x)
drills
Ø
Fronttafel-Ausschnitt
412 x 272 [mm]
Front panel cut-out