USER MANUAL 1.10 | DC1000 DIALOG-CONTROLLER
Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com
2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx
107
4.5.1. Technical data
Module data
Versions / part no.
Only available as a built-in module
Dimensions, WxH[mm]
56.6 x 108
Weight
Approx. 100 g
Operating temperature
range
5 °C to 55 °C (condensation free)
Convection cooling ensured and slot A3 not used
EMI, protection class, insulation test, protection type (installed)
Interference emission
EN 61000-6-4, industrial application
Interference resistance
EN 61000-6-2, industrial application (connector cable < 30 m)
Protection class
III
Insulation resistance
EN 61131-2; DC 500 V test voltage
Protection type
IP 20
Supply voltage, current consumption
Module electronics power
supply (connection voltage)
SELV DC +24 V (-15 % / +20 %) < 0.4 A (EN 61131-2)
alternating voltage component max. 5 %
I/O power supply
DC +24 V (EN 61131-2) together with module supply
Current consumption
At U
e
= DC +24 V in neutral, max. 500 mA,
fusing based on I/O load, max. 12 A
Protection against supply
voltage pole reversal
Yes
Potential isolation
No
Digitale inputs/outputs (DIO)
Number of inputs
8 (X2), up to 8 of which can be used as +24 V encoder inputs;
counter frequency at 4x evaluation < 40 kHz
Number of inputs/outputs
8 (X1)
Output current
0.5 A
Short circuit protection
Yes
Potential isolation
No
Connection technique
Standing front wiring for terminal strips (not part of the scope of supply)
Analog inputs/outputs
Inputs
4 analog ±10 V inputs
Inputs/Outputs
4 analog ±10 V or ±20 mA inputs/outputs
Resolution
Min. 16 bit
Connection technique
Standing front wiring for terminal strips (not part of the scope of supply)